Air-Insulated Disconnector (11–36 kV): Selection & Application Guide
An air-insulated disconnector (air-break switch / isolator) provides visible, off-load isolation of medium-voltage overhead lines for safe maintenance and sectionalising. A fused version adds current-limiting fuses to also clear downstream short-circuit faults.
Air-Insulated Disconnector (off-load)
moving blade (off-load only)
Off-load isolator vs fused isolator vs load-break
| Device | Interrupts load? | Interrupts fault? | Typical use |
|---|---|---|---|
| Plain disconnector | No | No | Visible isolation / sectionalising |
| Fused isolator | No | Yes (via fuse) | Isolation + feeder/transformer protection |
| Load-break switch | Yes | Yes | Switching load + fault |
Typical ratings
| Parameter | Values |
|---|---|
| Voltage classes | 11, 24, 33 / 36 kV |
| Continuous current | 200–630 A (up to 1250 A on some designs) |
| Standards | IEC 62271-102, IEC 62271-1 |
| Pollution / creepage | Per IEC 60815 |
Selection guide
Use a plain disconnector for isolation only; choose a fused isolator when you also need short-circuit protection of the lateral feeder or transformer. Confirm phase-to-earth clearance and pole-mounting height against the utility spec. Our detailed guides cover types, ratings and field maintenance.
33 kV Air-Insulated Outdoor Disconnector with Current-Limiting Fuses
Pole-Mounted Air-Insulated Disconnector — Types, Ratings & Selection
Pole-Mounted Disconnector — Installation, Operation & Maintenance
Frequently Asked Questions
What ratings are typical for pole-mounted air disconnectors?
Commonly 11, 24 and 33/36 kV classes with continuous currents of 200-630 A (up to 1250 A for some designs), conforming to IEC 62271-102.
Can an air disconnector break load or fault current?
No. It is an isolating device for off-load conditions only; load or fault current must be switched by a load-break switch, circuit breaker or fuse.
How do I choose between a disconnector and a fused isolator?
Use a plain disconnector for isolation only; use a fused isolator when you also need short-circuit protection of the lateral feeder or transformer.
Which standards apply?
IEC 62271-102 (AC disconnectors) and IEC 62271-1, with creepage and pollution per IEC 60815.