Air-Insulated Disconnector (11–36 kV): Selection & Application Guide

An air-insulated disconnector (air-break switch / isolator) provides visible, off-load isolation of medium-voltage overhead lines for safe maintenance and sectionalising. A fused version adds current-limiting fuses to also clear downstream short-circuit faults.

33 kV three-phase off-load disconnector — visible isolation for 11–36 kV overhead networks.

Air-Insulated Disconnector (off-load)

moving blade (off-load only)

Fused isolator assembly: combines visible disconnecting with expulsion-fuse fault protection.

Off-load isolator vs fused isolator vs load-break

Device Interrupts load? Interrupts fault? Typical use
Plain disconnector No No Visible isolation / sectionalising
Fused isolator No Yes (via fuse) Isolation + feeder/transformer protection
Load-break switch Yes Yes Switching load + fault

Typical ratings

Parameter Values
Voltage classes 11, 24, 33 / 36 kV
Continuous current 200–630 A (up to 1250 A on some designs)
Standards IEC 62271-102, IEC 62271-1
Pollution / creepage Per IEC 60815

Selection guide

Use a plain disconnector for isolation only; choose a fused isolator when you also need short-circuit protection of the lateral feeder or transformer. Confirm phase-to-earth clearance and pole-mounting height against the utility spec. Our detailed guides cover types, ratings and field maintenance.

33 kV Air-Insulated Outdoor Disconnector with Current-Limiting Fuses

Pole-Mounted Air-Insulated Disconnector — Types, Ratings & Selection

Pole-Mounted Disconnector — Installation, Operation & Maintenance

Frequently Asked Questions

What ratings are typical for pole-mounted air disconnectors?

Commonly 11, 24 and 33/36 kV classes with continuous currents of 200-630 A (up to 1250 A for some designs), conforming to IEC 62271-102.

Can an air disconnector break load or fault current?

No. It is an isolating device for off-load conditions only; load or fault current must be switched by a load-break switch, circuit breaker or fuse.

How do I choose between a disconnector and a fused isolator?

Use a plain disconnector for isolation only; use a fused isolator when you also need short-circuit protection of the lateral feeder or transformer.

Which standards apply?

IEC 62271-102 (AC disconnectors) and IEC 62271-1, with creepage and pollution per IEC 60815.