Lightning Arresters & Surge Arresters for 3–216 kV Systems

A lightning (surge) arrester is a gapless metal-oxide protective device that clamps transient overvoltages on a power network to a safe level, protecting transformers, switchgear, capacitor banks and lines. This pillar page explains polymer (composite) arrester construction, the key ratings, the international standards (IEC 60099-4, IEEE C62.11, GB 11032) and a step-by-step selection method, and links to every arrester model we supply from 6 kV to 216 kV.

What Is a Lightning / Surge Arrester?

A modern surge arrester is built around a stack of zinc-oxide (ZnO) varistor blocks. At the normal system voltage the blocks present a very high resistance and pass almost no current; when a lightning or switching surge arrives they become highly conductive and divert the energy to earth, then automatically return to the blocking state once the transient ends. Because there is no series spark gap, the protective level stays low and the device is sealed and maintenance-free. Gapless polymer arresters are the standard for 11 kV and 33 kV distribution, substations and industrial networks.

Polymer (Composite) vs Porcelain Arresters

Both use the same ZnO varistor core, but differ in the housing:

Aspect Polymer / Composite Porcelain
Housing Silicone-rubber or EPDM weather shed on FRP core Glazed ceramic
Weight Light (~1/3 of porcelain), easy to handle Heavy, fragile
Anti-pollution Hydrophobic, good in coastal/industrial areas Needs more creepage / washing
Breakage No shattering, vandal resistant Can crack on impact
Best use Distribution poles, exposed lines, compact gear Legacy stations, easy stock

Types of Surge Arresters

  • Distribution arrester — pole- and pad-mounted units for 6–36 kV networks (our 6/9/12/15/24/33/36 kV polymer range).
  • Station (heavy-duty) arrester — higher line-discharge class and 10–20 kA rating for substations and capacitor banks.
  • Line arrester — compact units fitted directly on overhead conductors to limit back-flashover on exposed spans.
  • Capacitor / special arrester — including drop-out types that disconnect on failure (see our capacitor drop-out arrester).
  • Neutral / transformer-terminal arrester — sized to the equipment’s basic insulation level (BIL).

Key Ratings — How to Read an Arrester Nameplate

Five parameters define the duty of an arrester:

  1. Rated voltage Ur — the maximum continuous permissible rms voltage; must exceed the temporary overvoltage (TOV).
  2. Continuous operating voltage Uc (MCOV) — the steady-state voltage the arrester carries without ageing.
  3. Nominal discharge current In — the reference impulse current (5 kA / 10 kA distribution, up to 20 kA station).
  4. Residual voltage Up at In — the protective level, including the lightning-impulse (8/20 µs) residual voltage.
  5. Line discharge class (1–5) — energy absorption for downed-line / back-flashover surges; plus the creepage distance for the pollution class.

International Standards (IEC, IEEE, GB)

Arresters are qualified to IEC 60099-4 (metal-oxide surge arresters without gaps for a.c. systems), with selection guidance in IEC 60099-5 and general rules in IEC 60099-1; the Chinese national equivalent is GB 11032. In North America, IEEE C62.11 (arresters for a.c. circuits above 1 kV) and IEEE C62.22 (application guide) apply. Routine tests — including the discharge and residual-voltage checks — follow IEC 60099-4 Clause 9.1. Our polymer arresters are type-tested to these standards; request the type-test report for your model.

How to Select a Surge Arrester (6 Steps)

  1. Determine the system voltage class (e.g., 11 kV or 33 kV) and the neutral earthing method.
  2. Calculate the temporary overvoltage (TOV) and choose Ur above it with margin.
  3. Set Uc (MCOV) to the maximum continuous phase-to-ground voltage of the network.
  4. Pick In (5 kA / 10 kA / 20 kA) and the line-discharge class from feeder length and exposure.
  5. Confirm the residual voltage Up is compatible with the protected equipment’s BIL.
  6. Set the creepage distance for the local pollution class and verify certifications (IEC/GB type test, ISO 9001). We can match any model to your single-line diagram.

Applications

Surge arresters protect transformer terminals, capacitor banks, cable heads and substation busbars, pole-top 11 kV and 33 kV distribution lines, and the incoming side of switchgear and motors. On lightning-prone rural networks and coastal or industrial corridors, polymer arresters with adequate line-discharge class are the first line of defence for continuity of supply.

Related Products and Guides

Polymer lightning arrester models:

Related protection equipment:

Frequently Asked Questions

What is the difference between a lightning arrester and a surge arrester?

The two names refer to the same device — a metal-oxide (ZnO) protective unit that clamps transient overvoltages on a power network to a safe level. ‘Lightning arrester’ is the older term tied to direct lightning strokes; ‘surge arrester’ covers all switching and lightning surges. Modern gapless polymer arresters protect distribution (11–36 kV), sub-transmission and station equipment against both. We use the terms interchangeably below.

What does a polymer (composite) arrester consist of?

A polymer arrester has a stack of metal-oxide varistor (MOV) blocks housed in a hollow or solid polymer (silicone-rubber or EPDM) weather shed on a fiberglass core, terminated by metal end fittings. There is no series spark gap. The ZnO blocks change resistance with voltage: near-infinite at the system voltage, near-zero during a surge, so they divert the current to earth and recover automatically after the transient passes.

Which ratings matter when selecting an arrester?

Five ratings define an arrester: (1) rated voltage Ur — the maximum continuous permissible rms voltage; (2) continuous operating voltage Uc (MCOV); (3) nominal discharge current In (typically 5 kA or 10 kA for distribution, up to 20 kA for stations); (4) residual voltage Up at In — the protective level; and (5) line discharge class (1–5) — energy handling. Creepage distance sets the pollution class. Confirm each value against your system’s temporary overvoltage.

Which standards apply to surge arresters?

The governing standards are IEC 60099-4 (metal-oxide surge arresters without gaps for a.c. systems), IEC 60099-5 (selection and application recommendations) and IEC 60099-1 (general), with the Chinese equivalent GB 11032. In North America, IEEE C62.11 (arresters for a.c. circuits above 1 kV) and IEEE C62.22 (application guide) apply. Routine tests follow IEC 60099-4 Clause 9.1.

How do I select the rated voltage Ur for an 11 kV or 33 kV system?

Ur must exceed the highest temporary overvoltage (TOV) the arrester will see, including ground-fault and ferroresonance conditions. As a rule of thumb, an 11 kV (phase-to-phase) system often uses Ur ≈ 12–15 kV, and a 33 kV system Ur ≈ 30–36 kV, but the exact Ur depends on the neutral earthing method and fault-clearing time. Always calculate TOV from your single-line diagram rather than copying a catalogue value.

What is residual voltage / protective level, and why does it matter?

Residual voltage Up is the voltage that appears across the arrester terminals when a standard impulse current (8/20 µs at In) flows — it is the ceiling the protected equipment must withstand. A lower Up gives better insulation coordination and lets you specify lower BIL equipment, but the arrester must still survive the energy. Specifying Up is a trade-off between protection level and the arrester’s own duty.

What is line discharge class?

Line discharge class (IEC 60099-4 classes 1–5) rates an arrester’s energy absorption from a downed-line or back-flashover surge — the longer and more exposed the feeder, the higher the class needed. A Class 1 arrester suits a short, shielded urban feeder; a Class 3–5 arrester is used on long overhead lines and exposed rural networks such as 11 kV and 33 kV distribution in lightning-prone regions.

Where are surge arresters used and how long do they last?

Surge arresters are fitted at transformer terminals, capacitor banks, cable heads, substation busbars and pole-top distribution lines, and on the incoming side of switchgear and motors. Qualified polymer arresters are designed for 20–30 years; they are sealed and maintenance-free, but line crews should visually check the housing for tracking, erosion or cracking during routine inspections, and add a surge counter where fault statistics are needed.